New Guideline Specifications for AMCA-Certified Products
By JOSH PARENT, AMCA International Inc., Arlington Heights IL
In 2018, AMCA started a free specification-review service. What it is finding is most specifications are ineffectively written with regard to certification, leaving the door open for non-certified products to be installed where certified products were intended. Based on feedback from specifying engineers, AMCA recently simplified its guideline specifications, reducing paragraph-long statements to single sentences. Engineers are encouraged to incorporate this new and more efficient language into their specifications.
FANS
Agricultural Fans
- All fans shall bear the AMCA Certified Ratings Program seal for CFM/Watt and Air Performance;
- All fans shall bear the AMCA Certified Ratings Program seal for Fan Energy Index (FEI).
Air-Circulating Fans
- All fans shall bear the AMCA Certified Ratings Program seal for Air Performance;
- All fans shall bear the AMCA Certified Ratings Program seal for FEI.
Air-Curtain Units
- All air-curtain units shall bear the AMCA Certified Ratings Program seal for Air Performance;
- All air-curtain units shall bear the AMCA Certified Ratings Program seal for Air and Sound Performance.
Axial Fans, Ceiling Ventilators, Centrifugal Fans, Mixed-Flow Fans, Power Roof Ventilators, and Propeller Fans
- All fans shall bear the AMCA Certified Ratings Program seal for Air Performance;
- All fans shall bear the AMCA Certified Ratings Program seal for Air and Sound Performance;
- All fans shall bear the AMCA Certified Ratings Program seal for Air Performance and Efficiency;
- All fans shall bear the AMCA Certified Ratings Program seal for Air and Sound Performance and Efficiency;
- All fans shall bear the AMCA Certified Ratings Program seal for Air Performance and Fan Efficiency Grade (FEG);
- All fans shall bear the AMCA Certified Ratings Program seal for Air and Sound Performance and FEG;
- All fans shall bear the AMCA Certified Ratings Program seal for FEI.
Axial Impellers
- All axial impellers shall bear the AMCA Certified Ratings Program seal for Air Performance;
- All fans shall bear the AMCA Certified Ratings Program seal for FEI.
Induced-Flow Fans
- All fans shall bear the AMCA Certified Ratings Program seal for Induced Flow Fan Air Performance;
- All fans shall bear the AMCA Certified Ratings Program seal for Induced Flow Fan Air and Sound Performance;
- All fans shall bear the AMCA Certified Ratings Program seal for Induced Flow Fan Air Performance and FEG;
- All fans shall bear the AMCA Certified Ratings Program seal for Induced Flow Fan Air and Sound Performance and FEG;
- All fans shall bear the AMCA Certified Ratings Program seal for FEI.
Jet Tunnel Fans
- All fans shall bear the AMCA Certified Ratings Program seal for Jet Fan Air Performance;
- All fans shall bear the AMCA Certified Ratings Program seal for Jet Fan Air and Sound Performance;
- All fans shall bear the AMCA Certified Ratings Program seal for FEI.
Large-Diameter Ceiling Fans
- All fans shall bear the AMCA Certified Ratings Program seal for Air Performance.
Positive-Pressure Ventilators
- All positive-pressure ventilators shall bear the AMCA Certified Ratings Program seal for Air Performance.
Dampers
- All dampers shall bear the AMCA Certified Ratings Program seal for Air Performance;
- All dampers shall bear the AMCA Certified Ratings Program seal for Air Performance and Air Leakage;
- All dampers shall bear the AMCA Certified Ratings Program seal for Air Performance and Efficiency;
- All dampers shall bear the AMCA Certified Ratings Program seal for Air Performance, Air Leakage, and Efficiency.
Louvers
- All louvers shall bear the AMCA Certified Ratings Program seal for Air Performance;
- All louvers shall bear the AMCA Certified Ratings Program seal for Air and Sound Performance;
- All louvers shall bear the AMCA Certified Ratings Program seal for Air Performance and Water Penetration;
- All sand louvers shall be tested in accordance with ANSI/AMCA Standard 500-L and licensed to bear the AMCA Certified Ratings Program seal for Air Performance and Wind Driven Sand, in accordance with AMCA Publication 511;
- All louvers shall bear the AMCA Certified Ratings Program seal for Air Performance and Wind-Driven Rain;
- All louvers shall bear the AMCA Certified Ratings Program seal for Air Performance, Water Penetration, and Wind-Driven Rain;
- All louvers shall bear the AMCA Certified Ratings Program seal for Air and Sound Performance and Water Penetration;
- All louvers shall bear the AMCA Certified Ratings Program seal for Air Leakage.
Airflow-Measurement Stations
- All airflow-measurement stations shall bear the AMCA Certified Ratings Program seal for Air Performance.
Packaged Equipment
- Energy-Recovery Ventilators;
- All energy-recovery ventilators shall bear the AMCA Certified Ratings Program seal for Air Performance.
Evaporative Coolers
- All evaporative coolers shall bear the AMCA Certified Ratings Program seal for Air Performance;
- All evaporative coolers shall bear the AMCA Certified Ratings Program seal for Air and Sound Performance.
Single-Room Air Handlers
- All single-room air handlers shall bear the AMCA Certified Ratings Program seal for Air Performance;
- All single-room air handlers shall bear the AMCA Certified Ratings Program seal for Air and Sound Performance.
DUCTS
Spiral Ducts
- All spiral ducts shall bear the AMCA Certified Ratings Program seal for Air Leakage.
Prefabricated Duct Silencers
- All acoustical duct silencers shall bear the AMCA Certified Ratings Program seal for Air and Sound Performance.
Conclusion
To arrange a lunch-and-learn about specifying AMCA-certified products for your office, contact the author at (847) 704-6330 or [email protected].
As associate director of business development for AMCA International, Josh Parent communicates with buyers and specifiers of AMCA members’ products and provides education and training concerning the AMCA Certified Ratings Program.